Mounted Equipment Of Automatic Fire Extinguisher

For Explosion-Proof

▶ Description

The semiconductor, LCD manufacturing equipment, consisted of expensive equipment such as chemical liquid supply pressure explosion proof equipment in pz products for protection against fire, explosion proof certification deukhan Given the characteristics of the installation site.
(Receiver not included Product)

▶ Features

  • Unlike other extinguishing agents, it is safe and clean after extinguishment. It doesn't make any residue
  • Can be used in a Explosion-proof area
  • Protection applied to the inside of the fire extinguisher gas choice available - N2, AIR
  • A leakage compensation pressing method is convenient to maintain a constant pressure in the inside of the fire extinguishers

 

 

 

SPECIFICATION
Model NEX-1EG0141 NEX-2EG0231 NEX-3EG0461
Size
(mm)
W 500 400 570
D 337 379 379
H 1,120 1,570 1,570
Weight 76kg 110kg 182kg
Extinguishing
Containers
14kg x 1BOTTLE 23kg x 2BOTTLE 23kg x 2BOTTLE
Extinguishing
Agents
CO2,HFC-23,HFC-227ea(optionally available)
Protective
Gas Temperature
40℃ or less
Power DC 24V
Certification Standards Pz Explosion-Proof Pressure
Explosion Proof Grade Ex pz II T6
압력유지방식 Pressure leakage compensation method